Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, affectionately referred to as the 'circuit breaker,' a paragon of outdoor distribution switchgear specifically designed for a rated voltage of 12kV and a formidable three-phase AC of 50Hz. This adaptable circuit breaker expertly manages the interruption and connection of load current, overload current, and short circuit current within the power grid. It is equipped with advanced overload and short circuit protection features, adeptly meeting control and measurement requirements, while offering sophisticated remote control and monitoring capabilities. Its extensive applications cover substations, industrial environments, and mining enterprise distribution systems, delivering unmatched control and operation, making it ideal for settings with frequent operations.
Structural Features:
Meticulously crafted, the circuit breaker exhibits a three-phase pillar dry design;
Engineered with a fully enclosed structure, it provides exceptional sealing, outstanding moisture resistance, and anti-condensation properties, rendering it the optimal choice for high-temperature and humid regions;
Utilizes cutting-edge vacuum arc extinguishing technology for superior insulation reliability;
Offers impeccable opening and closing performance, ensuring safety with no risk of combustion or explosion;
Compact and lightweight, it requires no maintenance and promises a remarkable lifespan;
Versatile in operation with manual, electric, or remote control options available;
The operating mechanism is expertly sealed at the base of the switch box, effectively preventing outdoor environmental corrosion;
Features an innovative, minimalist design with a restless mechanism ensuring reliable dynamic performance, compact form, and an extraordinary service life of up to 10,000 cycles.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |