Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse (hereinafter referred to as "fuse") is designed for outdoor overhead distribution systems operating at a rated frequency of 50Hz and a rated voltage of 10kV (12/15/35/40.5). This essential device serves as a protective mechanism for circuits or electrical equipment, ensuring safety during power system overloads or short circuits. In its standard operating mode, the fuse integrates seamlessly into the power line, maintaining tension and securing the movable joint. Upon fault detection, the fault current activates the fuse, releasing the joint, swiftly dropping the fuse tube, and cutting the circuit—safeguarding both the line and equipment. Enhanced with elastic contacts and an arc extinguishing cover, the load type fuse is adept at managing load currents within the power system.
The fuse adheres to stringent technical standards including GB / T 15166.3 - 2008 for high voltage AC fuses - Part 3: injection fuses, as well as DL / T 640 - 1997 standards for outdoor AC high voltage drop tested fuses and fuse links ordering technical conditions.
Working Environment:
Ambient temperature: -40°C to +40°C;
Relative Humidity: Daily average not exceeding 95%, with a monthly average capped at 90%;
Altitude: Not exceeding 3000 meters;
Outdoor Wind Speed: Not surpassing 34 meters per second;
Installation Site Requirements: Free from fire, explosion hazards, and chemical corrosive gases, ensuring a well-ventilated environment.
Note: For conditions beyond these standard specifications, users are encouraged to negotiate with the company for customized solutions.
Technical Parameters
Note: Our company is committed to providing tailored products to meet specific user requirements.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |