Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The ZW32-12 outdoor high voltage vacuum circuit breaker, affectionately known as the 'circuit breaker,' is a remarkable outdoor distribution switchgear expertly engineered to function at a rated voltage of 12kV with a robust three-phase AC of 50Hz. This dynamic circuit breaker masterfully manages the interruption and connection of load current, overload current, and short circuit current within the power grid with exceptional ease. It is renowned for its cutting-edge overload and short circuit protective capabilities, flawlessly meeting control and measurement specifications while offering advanced remote control and monitoring functionalities. Its extensive applicability encompasses substations, industrial settings, and mining enterprise distribution systems, delivering unmatched control and operation—perfect for demanding environments with frequent operations.
Structural features:
Crafted with meticulous precision, the circuit breaker features a sophisticated three-phase pillar dry design;
Engineered with an impeccably sealed, fully enclosed structure that provides superior sealing, remarkable moisture resistance, and anti-condensation properties, making it an ideal solution for high-temperature and humid regions;
Utilizes advanced vacuum arc extinguishing technology to ensure exceptional insulation reliability;
Offers flawless opening and closing performance, guaranteeing safety with no risk of combustion or explosion;
Compact, lightweight, maintenance-free, and promises an outstanding lifespan;
Versatility in operation, with manual, electric, or remote control options available;
The operating mechanism is elegantly sealed at the base of the switch box, providing effective protection against outdoor environmental corrosion;
Presents an innovative, simplistic design with a restless mechanism that assures reliable dynamic performance, a compact form, and an extraordinary service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |