Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, a groundbreaking innovation tailored for modern outdoor distribution networks. Affectionately dubbed the 'circuit breaker,' this advanced piece of switchgear is precisely crafted for use with a 12kV rated voltage and robust three-phase AC operating at 50Hz. This versatile circuit breaker deftly handles the interruption and reconnection of load currents, overload currents, and short circuit currents within power grids. It boasts state-of-the-art overload and short circuit protection capabilities, effortlessly catering to control and measurement requirements, while simultaneously providing advanced remote control and monitoring functionalities. Its broad spectrum of applications covers substations, industrial sectors, and mining enterprise distribution systems, making it the premier choice for environments demanding frequent operations, delivering unparalleled control, safety, and efficiency.
Structural Features:
Meticulously crafted with a refined three-phase pillar dry design that embodies precision and excellence;
Expertly engineered with a fully enclosed structure, this breaker provides superior sealing, extraordinary moisture resistance, and anti-condensation capabilities, perfectly suited for high-temperature and humid conditions;
Utilizes cutting-edge vacuum arc extinguishing technology, offering unparalleled insulation reliability;
Ensures impeccable opening and closing performance, guaranteeing safety without any risk of combustion or explosion;
Designed to be compact and lightweight, this breaker is maintenance-free, boasting an impressive lifespan;
Features adaptable operation with options for manual, electric, or remote control, catering to diverse needs;
The operating mechanism is meticulously sealed at the base of the switch box, effectively safeguarding it from outdoor environmental corrosion;
Showcases a revolutionary and streamlined design with a restless mechanism, ensuring reliable dynamic performance, a compact structure, and an astonishing service life spanning up to 10,000 cycles.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |