Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the exceptional ZW32-12 outdoor high voltage vacuum circuit breaker, fondly referred to as the 'circuit breaker.' This outstanding piece of outdoor distribution switchgear is meticulously designed to function at a rated voltage of 12kV, supported by a robust three-phase AC of 50Hz. This highly adaptable circuit breaker is expertly engineered to manage the interruption and connection of load current, overload current, and short circuit current within the power grid, making it an indispensable component. It features highly advanced overload and short circuit protective capabilities, meeting and exceeding control and measurement standards with refined remote control and monitoring functionalities. Its extensive application spans across substations, industrial domains, and mining enterprise distribution systems, delivering unmatched control and operation, perfectly suited for environments with frequent operational demands.
Structural features:
Crafted with meticulous precision, the circuit breaker stands out with its three-phase pillar dry design, a hallmark of engineering excellence;
Engineered with a fully enclosed structure, it provides superior sealing, exceptional resistance to moisture, and anti-condensation properties, making it the ideal selection for high-temperature and humid regions;
Employs cutting-edge vacuum arc extinguishing technology, delivering extraordinary reliability in insulation;
Ensures flawless opening and closing performance, guaranteeing safety with zero risk of combustion or explosion;
Compact and lightweight, requiring no maintenance and promising an impressive lifespan that redefines durability;
Versatile in operation, offering manual, electric, or remote control options for ultimate flexibility and convenience;
The operating mechanism is meticulously sealed at the base of the switch box, providing an effective shield against environmental corrosion from outdoor elements;
Exhibits a novel, simplistic design with a resilient mechanism that ensures reliable dynamic performance, a compact form, and an astounding service life reaching up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |