Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The ZW32-12 outdoor high voltage vacuum circuit breaker, endearingly termed the 'circuit breaker,' is an outstanding piece of outdoor distribution switchgear. It operates efficiently at a rated voltage of 12kV with a powerful three-phase AC frequency of 50Hz. This adaptable circuit breaker adeptly manages the interruption and connection of load current, overload current, and short circuit current within the power grid. It features cutting-edge overload and short circuit protection capabilities, seamlessly meeting control and measurement requirements while offering sophisticated remote control and monitoring functionalities. Widely used in substations, industrial environments, and mining enterprise distribution systems, it provides unrivaled control and operation, making it ideal for settings with frequent operational demands.
Structural features:
Expertly crafted, the circuit breaker boasts a three-phase pillar dry design;
Designed with a fully enclosed structure, it excels in superb sealing, exceptional moisture resistance, and anti-condensation properties, making it an ideal choice for high-temperature and humid regions;
Incorporates advanced vacuum arc extinguishing technology, ensuring outstanding insulation reliability;
Provides impeccable opening and closing performance, ensuring safety with no risk of combustion or explosion;
Compact and lightweight, it requires no maintenance and promises an impressive lifespan;
Offering versatility in operation, with options for manual, electric, or remote control;
The operating mechanism is securely sealed at the base of the switch box, effectively protecting against outdoor environmental corrosion;
Presents an innovative, simplistic design with a dynamic mechanism that guarantees reliable performance, a compact form, and an extraordinary service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |