Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 outdoor high voltage vacuum circuit breaker, popularly known as the 'circuit breaker.' This exceptional piece of outdoor distribution switchgear is masterfully engineered to operate with a rated voltage of 12kV and a formidable three-phase AC of 50Hz. This dynamic and versatile circuit breaker excels in the art of interrupting and connecting load current, overload current, and short circuit current within the power grid. It is endowed with cutting-edge overload and short circuit protection capabilities, meeting control and measurement requirements with unparalleled precision. Experience the future of remote control and monitoring functionalities with this advanced circuit breaker. Its extensive applications stretch across substations, industrial sectors, and mining enterprise distribution systems, offering unmatched control and operational excellence—an ideal choice for environments demanding frequent operations.
Structural features:
Meticulously crafted with precision, the circuit breaker features a sophisticated three-phase pillar dry design, exemplifying excellence in engineering.
Expertly engineered with a fully enclosed structure, this breaker provides superior sealing, remarkable moisture resistance, and exceptional anti-condensation features, making it the ideal solution for high-temperature and humid regions.
Incorporating state-of-the-art vacuum arc extinguishing technology, it ensures outstanding insulation reliability, setting a benchmark in safety standards.
Delivers impeccable opening and closing performance, guaranteeing safety with no risk of combustion or explosion, ensuring peace of mind in every operation.
This compact, lightweight marvel requires no maintenance and promises an extraordinary lifespan, redefining efficiency in the world of circuit breakers.
Versatility redefined with options for manual, electric, or remote control operations, allowing seamless integration into various operational workflows.
The operating mechanism is strategically and meticulously sealed at the base of the switch box, providing robust protection against the harshest outdoor environmental corrosion.
Boasting a novel and simplistic design, it features a restless mechanism that ensures reliable dynamic performance, a compact form factor, and an astonishing service life of up to 10,000 cycles, setting a new standard in the industry.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |