Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Discover the ZW32-12 outdoor high voltage vacuum circuit breaker, fondly referred to as the 'circuit breaker' – an exceptional piece of outdoor distribution switchgear. Masterfully engineered to perform at an impressive rated voltage of 12kV, this powerhouse operates with a robust three-phase AC frequency of 50Hz. The circuit breaker seamlessly manages the interruption and connection of load, overload, and short circuit currents within the power grid with remarkable efficiency. It is equipped with cutting-edge overload and short circuit protective features, adeptly meeting control and measurement demands while offering sophisticated remote monitoring and control capabilities. Widely utilized in substations, industrial landscapes, and mining enterprise distribution networks, it provides unmatched control and operation, making it the ideal solution for environments requiring frequent and reliable operations.
Structural features:
Crafted with meticulous precision, the circuit breaker features an innovative three-phase pillar dry design;
Expertly engineered with a fully enclosed structure, this circuit breaker delivers superior sealing capabilities, boasting exceptional moisture resistance and anti-condensation properties, making it the optimal choice for regions with high temperatures and humidity;
Utilizes cutting-edge vacuum arc extinguishing technology to ensure outstanding insulation reliability, setting a new standard for safety and performance;
Achieves flawless opening and closing operations, ensuring unparalleled safety by eliminating any risk of combustion or explosion;
Designed to be compact and lightweight, this circuit breaker requires no maintenance and promises an impressive lifespan, truly redefining longevity in electrical components;
Offers remarkable versatility in operation with manual, electric, and remote control options, catering to diverse operational needs;
The operating mechanism is meticulously sealed at the base of the switch box, providing enhanced protection against corrosive outdoor environments;
Exhibits a novel, streamlined design incorporating a reliable restless mechanism, ensuring consistent dynamic performance, a compact form factor, and an astounding service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |