The cutting-edge S-M series three-phase oil-immersed transformer is engineered with a fully oil-filled, sealed corrugated oil tank. Its unique design intelligently adapts to the oil's expansion through its elastic construction, meeting rigorous heat dissipation demands. This model is celebrated for its high efficiency, low energy loss, and
exceptional power-saving capabilities, significantly reducing operational costs. Its robust design finds extensive use in power plants, substations, industrial and mining enterprises, ports, airports, and environmentally-conscious sites.
Standard Compliance: Adheres to IEC60076-1, IEC60076-2, IEC60076-3, IEC60076-5, IEC60076-10.
1. Ambient temperature range: maximum +40°C, minimum -25ºC.
2. Temperature standards: Average hottest month: +30ºC, yearly average: +20ºC.
3. Recommended altitude: Not exceeding 1000 meters.
4. Voltage waveform: Should closely resemble a sine wave.
5. Balance in power: Three-phase supply voltage should be symmetrical.
6. Harmonic content: Load current total harmonics must not surpass 5% of rated current.
7. Installation versatility: Usable indoors or outdoors.
1. Boasts high efficiency, minimal loss, and operates with low noise.
2. Durable design with high mechanical strength and superior short-circuit resilience.
3. Reduced load and no-load loss for optimal performance.
4. Compact, dependable, with long-lasting service life, and maintenance-free.
Innovative Structure
Iron core:
Iron core:
Crafted from premium high-performance, high-permeability silicon steel sheets for minimal no-load loss.
Advanced High/Low Voltage Winding:
Winding strategies: 500KVA and below utilize layer type, while 630KVA and beyond employ a new spiral design.
Features include high mechanical strength, balanced ampere-turn distribution, and excellent short-circuit resistance.
Fully Sealed Structure:
Utilizes vacuum oil filling in packaging to completely eliminate moisture, ensuring the transformer oil remains uncontaminated and free from air exposure. This innovation prevents oil aging, enhancing operational reliability.
Enhanced Positioning Structure:
Incorporates a positioning framework to avert displacement during transport, complemented by securely fastened components.
Expertly equipped with high-quality fastening nuts, this ensures that our fasteners remain securely in place even during extended operation periods, providing unmatched stability and reliability for the product.
Sophisticated Oil Tank Design:
The oil tank features an advanced corrugated design, offering a straightforward manufacturing process, exceptional mechanical strength, and superior welding performance. Its design minimizes leakage risks while the excellent oil fluidity enhances the overall heat dissipation capacity, boosting product efficiency.
Enhanced Configuration Features:
Furnished with a precision pressure relief valve and a reliable signal thermometer, our transformer guarantees unparalleled safety and optimal operation.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
130 | 630/600 | 2.3 | 4 | 745 | 530 | 890 | 280 |
50 | 170 | 910/870 | 2 | 790 | 560 | 940 | 365 | |||||
63 | 200 | 1090/1040 | 1.9 | 820 | 570 | 950 | 425 | |||||
80 | 250 | 1310/1250 | 1.9 | 850 | 580 | 1000 | 485 | |||||
100 | 290 | 1580/1500 | 1.8 | 900 | 620 | 1010 | 540 | |||||
125 | 340 | 1890/1800 | 1.7 | 880 | 630 | 1050 | 610 | |||||
160 | 400 | 2310/2200 | 1.6 | 950 | 690 | 1120 | 710 | |||||
200 | 480 | 2730/2600 | 1.5 | 990 | 730 | 1200 | 835 | |||||
250 | 560 | 3200/3050 | 1.4 | 1180 | 700 | 1200 | 970 | |||||
315 | 670 | 3830/3650 | 1.4 | 1230 | 760 | 1250 | 1125 | |||||
400 | 800 | 4520/4300 | 1.3 | 1260 | 800 | 1300 | 1310 | |||||
500 | 960 | 5410/5150 | 1.2 | 1400 | 900 | 1320 | 1530 | |||||
630 | Dyn11 Yyn0 Yzn11 |
1200 | 6200 | 1.1 | 4.5 | 1530 | 940 | 1350 | 1890 | |||
800 | 1400 | 7500 | 1 | 1580 | 1000 | 1420 | 2185 | |||||
1000 | 1700 | 10300 | 1 | 1770 | 1180 | 1450 | 2480 | |||||
1250 | 1950 | 12000 | 0.9 | 1920 | 1290 | 1430 | 3020 | |||||
1600 | 2400 | 14500 | 0.8 | 1990 | 1340 | 1620 | 3550 | |||||
2000 | 3000 | 17100 | 0.7 | 5 | 1950 | 1680 | 2100 | 4530 | ||||
2500 | 3300 | 23200 | 0.7 | 2020 | 1710 | 2100 | 5030 |
Note 1: For transformers with a rated capacity of 500kVA and below, the load loss values displayed above the diagonal line in the table pertain to the Dyn11 or Yzn11 coupling group, whereas those below apply to the Yyn0 coupling group.
Note 2: Achieve peak operational efficiency when the transformer's annual load rate averages between 35% and 40% by utilizing the loss values specified in the table.
Overall and Mounting Dimensions (mm)
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
100 | 630/600 | 1.5 | 4 | 690 | 510 | 920 | 275 |
50 | 130 | 910/870 | 1.3 | 730 | 510 | 960 | 340 | |||||
63 | 150 | 1090/1040 | 1.2 | 750 | 550 | 1000 | 385 | |||||
80 | 180 | 1310/1250 | 1.2 | 790 | 620 | 1020 | 450 | |||||
100 | 200 | 1580/1500 | 1.1 | 790 | 700 | 1040 | 520 | |||||
125 | 240 | 1890/1800 | 1.1 | 840 | 800 | 1070 | 625 | |||||
160 | 280 | 2310/2200 | 1 | 1070 | 670 | 1130 | 695 | |||||
200 | 340 | 2730/2600 | 1 | 1140 | 750 | 1140 | 795 | |||||
250 | 400 | 3200/3050 | 0.9 | 1200 | 800 | 1190 | 955 | |||||
315 | 480 | 3830/3650 | 0.9 | 1300 | 860 | 1210 | 1085 | |||||
400 | 570 | 4520/4300 | 0.8 | 1380 | 900 | 1240 | 1290 | |||||
500 | 680 | 5410/5100 | 0.8 | 1450 | 950 | 1300 | 1590 | |||||
630 | Dyn11 Yyn0 Yzn11 |
810 | 6200 | 0.6 | 4.5 | 1500 | 970 | 1360 | 1850 | |||
800 | 980 | 7500 | 0.6 | 1660 | 1140 | 1400 | 2210 | |||||
1000 | 1150 | 10300 | 0.6 | 1690 | 1190 | 1530 | 2570 | |||||
1250 | 1360 | 12000 | 0.5 | 1760 | 1230 | 1600 | 3115 | |||||
1600 | 1640 | 14500 | 0.5 | 1800 | 1250 | 1660 | 3520 | |||||
2000 | 1940 | 18300 | 0.4 | 5 | 1930 | 1360 | 1490 | 4060 | ||||
2500 | 2290 | 21200 | 0.4 | 2080 | 1360 | 1570 | 5105 |
Note 1: For transformers with a rated capacity of 500kVA and below, the load loss values above the diagonal line in the table are valid for the Dyn11 or Yzn11 coupling group, whereas those below apply to the Yyn0 coupling group.
Note 2: The highest operational efficiency can be reached when the average annual load rate is between 35% and 40%, using the loss values in the table.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
80 | 630/600 | 1.5 | 4 | 685 | 490 | 860 | 260 |
50 | 100 | 910/870 | 1.3 | 725 | 520 | 955 | 365 | |||||
63 | 110 | 1090/1040 | 1.2 | 750 | 535 | 970 | 415 | |||||
80 | 130 | 1310/1250 | 1.2 | 770 | 565 | 985 | 465 | |||||
100 | 150 | 1580/1500 | 1.2 | 800 | 595 | 1000 | 545 | |||||
125 | 170 | 1890/1800 | 1.1 | 815 | 670 | 1010 | 585 | |||||
160 | 200 | 2310/2200 | 1.1 | 1015 | 645 | 1055 | 695 | |||||
200 | 240 | 2730/2600 | 1 | 1020 | 650 | 1115 | 810 | |||||
250 | 290 | 3200/3050 | 1 | 1140 | 730 | 1120 | 930 | |||||
315 | 340 | 3830/3650 | 0.9 | 1195 | 785 | 1175 | 1075 | |||||
400 | 410 | 4520/4300 | 0.9 | 1265 | 855 | 1195 | 1255 | |||||
500 | 480 | 5410/5100 | 0.8 | 1325 | 915 | 1240 | 1435 | |||||
630 | Dyn11 Yyn0 Yzn11 |
570 | 6200 | 0.8 | 4.5 | 1465 | 960 | 1295 | 1880 | |||
800 | 700 | 7500 | 0.6 | 1515 | 995 | 1340 | 2145 | |||||
1000 | 830 | 10300 | 0.6 | 1605 | 1095 | 1460 | 2455 | |||||
1250 | 970 | 12000 | 0.5 | 1685 | 1145 | 1485 | 2840 | |||||
1600 | 1170 | 14500 | 0.5 | 1775 | 1225 | 1580 | 3310 | |||||
2000 | 1550 | 18300 | 0.4 | 5 | 1855 | 1265 | 1600 | 3960 | ||||
2500 | 1830 | 21200 | 0.4 | 1885 | 1305 | 1780 | 4980 |
Note 1: For transformers with a rated capacity of 500kVA and below, load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 coupling group, while values below apply to the Yyn0 coupling group.
Note 2: To achieve maximum operational efficiency, aim for an average annual load rate between 35% and 40%, referencing the table's loss values.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
80 | 505/480 | 1.5 | 4 | 785 | 710 | 880 | 370 |
50 | 100 | 730/695 | 1.3 | 800 | 730 | 940 | 480 | |||||
63 | 110 | 870/830 | 1.2 | 815 | 720 | 970 | 535 | |||||
80 | 130 | 1050/1000 | 1.2 | 830 | 740 | 990 | 580 | |||||
100 | 150 | 1260/1200 | 1.1 | 875 | 790 | 1010 | 705 | |||||
125 | 170 | 1510/1440 | 1.1 | 875 | 770 | 1050 | 775 | |||||
160 | 200 | 1850/1760 | 1 | 935 | 820 | 1140 | 975 | |||||
200 | 240 | 2180/2080 | 1 | 995 | 870 | 1140 | 1140 | |||||
250 | 290 | 2560/2440 | 0.9 | 995 | 900 | 1180 | 1240 | |||||
315 | 340 | 3060/2920 | 0.9 | 1030 | 880 | 1250 | 1425 | |||||
400 | 410 | 3610/3440 | 0.8 | 1075 | 910 | 1270 | 1635 | |||||
500 | 480 | 4330/4120 | 0.8 | 1120 | 930 | 1320 | 1950 | |||||
630 | Dyn11 Yyn0 Yzn11 |
570 | 4960 | 0.6 | 4.5 | 1165 | 950 | 1350 | 2150 | |||
800 | 700 | 6000 | 0.6 | 1210 | 1050 | 1390 | 2515 | |||||
1000 | 830 | 8240 | 0.6 | 1520 | 1020 | 1450 | 2635 | |||||
1250 | 970 | 9600 | 0.5 | 1630 | 1090 | 1540 | 3210 | |||||
1600 | 1170 | 11600 | 0.5 | 1680 | 1150 | 1600 | 3905 | |||||
2000 | 1550 | 14600 | 0.4 | 5 | 1890 | 1300 | 1600 | 4130 | ||||
2500 | 1830 | 16900 | 0.4 | 1990 | 1360 | 1700 | 5250 |
Note 1: For transformers with a rated capacity of 500kVA and below, refer to the load loss values above the diagonal line for the Dyn11 or Yzn11 coupling group, and below for the Yyn0 coupling group.
Note 2: For optimal efficiency, maintain an average annual load rate between 35% and 40% by implementing the loss values in the table.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
70 | 505 | 1.2 | 4 | 785 | 710 | 880 | / |
50 | 90 | 730 | 1.04 | 800 | 730 | 940 | / | |||||
80 | 115 | 1050 | 0.96 | 830 | 740 | 990 | / | |||||
100 | 135 | 1265 | 0.88 | 875 | 790 | 1010 | / | |||||
125 | 150 | 1510 | 0.88 | 875 | 770 | 1050 | / | |||||
160 | 180 | 1850 | 0.8 | 935 | 820 | 1140 | / | |||||
200 | 215 | 2185 | 0.8 | 995 | 870 | 1140 | / | |||||
250 | 260 | 2560 | 0.72 | 995 | 900 | 1180 | / | |||||
315 | 305 | 3065 | 0.72 | 1030 | 880 | 1250 | / | |||||
400 | 370 | 3615 | 0.64 | 1075 | 910 | 1270 | / | |||||
500 | 430 | 4330 | 0.64 | 1120 | 930 | 1320 | / | |||||
630 | 510 | 4960 | 0.48 | 4.5 | 1165 | 950 | 1350 | / | ||||
800 | 630 | 6000 | 0.48 | 1210 | 1050 | 1390 | / | |||||
1000 | 745 | 8240 | 0.48 | 1520 | 1020 | 1450 | / | |||||
1250 | 870 | 9600 | 0.4 | 1630 | 1090 | 1540 | / | |||||
1600 | 1050 | 11600 | 0.4 | 1680 | 1150 | 1600 | / | |||||
2000 | 1225 | 14640 | 0.32 | 5 | 1890 | 1300 | 1600 | / | ||||
2500 | 1440 | 14840 | 0.32 | 1990 | 1360 | 1700 | / |
Note 1: For transformers rated at 500kVA and below, the table's load loss values above the diagonal line pertain to the Dyn11 or Yzn11 coupling group, with those below for the Yyn0 group.
Note 2: Maximize efficiency when the transformer's average annual load rate is between 35% and 40%, by utilizing the table's loss values.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
65 | 455 | 1.2 | 4 | 785 | 710 | 880 | / |
50 | 80 | 655 | 1.04 | 800 | 730 | 940 | / | |||||
80 | 105 | 945 | 0.96 | 830 | 740 | 990 | / | |||||
100 | 120 | 1140 | 0.88 | 875 | 790 | 1010 | / | |||||
125 | 135 | 1360 | 0.88 | 875 | 770 | 1050 | / | |||||
160 | 160 | 1665 | 0.8 | 935 | 820 | 1140 | / | |||||
200 | 190 | 1970 | 0.8 | 995 | 870 | 1140 | / | |||||
250 | 230 | 2300 | 0.72 | 995 | 900 | 1180 | / | |||||
315 | 270 | 2760 | 0.72 | 1030 | 880 | 1250 | / | |||||
400 | 330 | 3250 | 0.64 | 1075 | 910 | 1270 | / | |||||
500 | 385 | 3900 | 0.64 | 1120 | 930 | 1320 | / | |||||
630 | 460 | 4460 | 0.48 | 4.5 | 1165 | 950 | 1350 | / | ||||
800 | 560 | 5400 | 0.48 | 1210 | 1050 | 1390 | / | |||||
1000 | 665 | 7415 | 0.48 | 1520 | 1020 | 1450 | / | |||||
1250 | 780 | 8640 | 0.4 | 1630 | 1090 | 1540 | / | |||||
1600 | 940 | 10440 | 0.4 | 1680 | 1150 | 1600 | / | |||||
2000 | 1085 | 13180 | 0.32 | 5 | 1890 | 1300 | 1600 | / | ||||
2500 | 1280 | 13360 | 0.32 | 1990 | 1360 | 1700 | / |
Note 1: For transformers boasting a rated capacity of 500kVA and below, the load loss values presented above the diagonal line in the table are tailored for the Dyn11 or Yzn11 coupling group, while the values found below this line are perfectly suited for the Yyn0 coupling group. This ensures optimal performance and adaptability to specific electrical configurations.
Note 2: When the transformer's average annual load rate hovers between 35% and 40%, you can achieve peak operating efficiency by adhering to the loss value indicated in the table. This strategic utilization of load values enables you to maximize the transformer's performance and efficiency effortlessly.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
25 | 20 10 6 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
63 | 600 | 1.7 | 5.5(20kV) 4 (6kV, 10kV) |
1090 | 600 | 1150 | / |
50 | 81 | 750 | 1.6 | 1120 | 620 | 1180 | / | |||||
100 | 130 | 1250 | 1.3 | 1150 | 650 | 1290 | / | |||||
160 | 189 | 1750 | 1.1 | 1160 | 675 | 1380 | / | |||||
250 | 270 | 2350 | 0.96 | 1200 | 880 | 1400 | / | |||||
315 | 324 | 2800 | 0.88 | 1230 | 920 | 1460 | / | |||||
400 | 387 | 3250 | 0.8 | 1250 | 950 | 1580 | / | |||||
500 | 459 | 3900 | 0.8 | 1390 | 960 | 1580 | / | |||||
630 | 540 | 4600 | 0.72 | 6(20kV) 4.5 (6kV, 10kV) |
1450 | 980 | 1600 | / | ||||
800 | 585 | 6000 | 0.64 | 1560 | 1020 | 1720 | / | |||||
1000 | 693 | 7600 | 0.56 | 1700 | 1070 | 1790 | / | |||||
1250 | 855 | 9500 | 0.56 | 1700 | 1070 | 1791 | / | |||||
1600 | 1080 | 12000 | 0.48 | 1850 | 1130 | 1850 | / | |||||
2000 | 1305 | 15000 | 0.48 | 6(20kV) 5 (6kV, 10kV) |
2000 | 1280 | 1980 | / | ||||
2500 | 1575 | 18500 | 0.4 | 2040 | 1320 | 2050 | / | |||||
3150 | 1980 | 23000 | 0.4 | 2200 | 1400 | 2250 | / |
Note 1: For transformers with rated capacity up to 500kVA, the load loss figures above the diagonal in the table cater to the Dyn11 or Yzn11 coupling group, while those below pertain to the Yyn0 coupling group. This differentiation ensures precise alignment with various coupling configurations, enhancing operational reliability.
Note 2: Achieve supreme operational efficiency when the transformer's average annual load rate sits between 35% and 40% by applying the table's loss values. This approach guarantees optimal performance and energy savings, leveraging the transformer's capabilities to their fullest extent.