Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The ZW32-12 outdoor high voltage vacuum circuit breaker, fondly termed the 'circuit breaker,' stands as a pinnacle of outdoor distribution switchgear, thriving at a rated voltage of 12kV with a robust three-phase AC of 50Hz. This adaptable circuit breaker expertly navigates the interruption and connection of load current, overload current, and short circuit current within the power grid. It is endowed with cutting-edge overload and short circuit protective capabilities, effortlessly meeting control and measurement specifications while offering advanced remote control and monitoring functionalities. Its wide-ranging application covers substations, industrial settings, and mining enterprise distribution systems, providing unmatched control and operation—ideal for environments demanding frequent operations.
Structural features:
Crafted with meticulous precision, the circuit breaker boasts a three-phase pillar dry design;
Engineered with a fully enclosed structure, it ensures superior sealing, exceptional moisture resistance, and anti-condensation properties, rendering it the optimal choice for high-temperature and humid regions;
Incorporates cutting-edge vacuum arc extinguishing technology, ensuring outstanding insulation reliability;
Ensures flawless opening and closing performance, guaranteeing safety with no risk of combustion or explosion;
Compact and lightweight, it demands no maintenance and promises an impressive lifespan;
Versatility in operation with options for manual, electric, or remote control;
The operating mechanism is meticulously sealed at the base of the switch box, offering robust protection against outdoor environmental corrosion;
Features a novel, minimalist design with a persistent mechanism ensuring reliable dynamic performance, a compact form, and a remarkable service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |