Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse, hereinafter known as the 'fuse', is expertly designed for optimal performance in outdoor overhead distribution systems. Perfectly suited for systems with a rated frequency of 50Hz and rated voltage of 10kV (12/15/35/40.5), this fuse is the ultimate protective element for circuits and electrical equipment. In instances of power system overload or short circuit faults, this device ensures safety and reliability. Under normal conditions, the fuse is seamlessly integrated into the power line, maintaining a tensioned state with a securely locked movable joint. Should a line failure occur, the fault current triggers the fuse to blow, swiftly releasing the movable joint and dropping the fuse tube, thereby disconnecting the circuit. This crucial action provides indispensable safety protection for line and equipment maintenance. Enhanced with an elastic contact and an arc extinguishing cover, the load type fuse offers superior functionality by efficiently opening and closing the load current in the power system.
The fuse adheres to stringent technical standards including GB / T 15166.3 - 2008 high voltage AC fuses - Part 3: injection fuses, and DL / T 640 - 1997 outdoor AC high voltage drop tested fuses and fuse links ordering technical conditions, ensuring unparalleled reliability and quality.
Working Environment:
Ambient temperature: The device is designed to operate within a temperature range of -40°C to +40°C;
Relative humidity: Capable of withstanding a daily average not exceeding 95%, and a monthly average not exceeding 90%;
The fuse is suitable for installation locations where the altitude does not exceed 3000 meters;
Outdoor wind speed should remain under 34 meters/second for optimal performance;
Installation site: Ideal for environments free from fire, explosion hazards, and chemical corrosive gases, in a well-ventilated area.
Note: If operating conditions exceed the above normal use parameters, users are encouraged to consult directly with the company for tailored solutions.
Technical parameters
Note: Our company is fully equipped to supply customized products in accordance with specific user requirements.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |