Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 outdoor high voltage vacuum circuit breaker, affectionately referred to as the 'circuit breaker.' This exceptional piece of outdoor distribution switchgear is engineered to perform flawlessly at a rated voltage of 12kV, with a powerful three-phase AC of 50Hz. Its versatility shines as it expertly manages the interruption and connection of load current, overload current, and short circuit current within the power grid. With cutting-edge overload and short circuit protective features, it seamlessly meets control and measurement specifications, while offering advanced remote control and monitoring capabilities. Widely utilized in substations, industrial domains, and mining enterprise distribution systems, it provides unparalleled control and operation, perfectly suited for environments requiring frequent operations.
Structural features:
Meticulously crafted with precision, this circuit breaker features a sophisticated three-phase pillar dry design;
Boasting a fully enclosed structure, it delivers superior sealing, exceptional moisture resistance, and anti-condensation properties, making it ideal for high-temperature and humid regions;
Utilizes cutting-edge vacuum arc extinguishing technology, ensuring outstanding insulation reliability;
Excels in providing flawless operational performance with safe opening and closing, eliminating risks of combustion or explosion;
Designed to be compact and lightweight, it requires no maintenance and promises a remarkable lifespan;
Offers versatile operational modes including manual, electric, or remote control;
The operating mechanism is meticulously sealed at the base of the switch box, effectively shielding it from outdoor environmental corrosion;
Exhibits a novel, streamlined design featuring a restless mechanism that ensures reliable dynamic performance, a compact form, and an extraordinary service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |